Part Details | DUCT TYPE AIR COOLING COIL
4130-00-276-9666 A unit consisting of parallel tubes joined together by a header on headers, utilizing fins to increase the surface area. designed to be used in conjunction with a duct in which a blower or fan is provided to circulate air through the unit to perform the function of cooling, heating , ventilating and/or dehumidifying (HVAC).
Alternate Parts: 43DWA, 4130-00-276-9666, 00-276-9666, 4130002769666, 002769666
Supply Group (FSG) | NSN Assigned | NIIN | Item Name Code (INC) |
---|---|---|---|
41 | JAN 01, 1963 | 00-276-9666 | 07530 ( COOLING COIL, AIR, DUCT TYPE ) |
REFERENCE DRAWINGS & PICTURES
Cross Reference | NSN 4130-00-276-9666
Part Number | Cage Code | Manufacturer |
---|---|---|
43DWA | 87103 | EDGE ELECTRONICS CORPORATIONDBA MC INTYRE COIL |
Technical Data | NSN 4130-00-276-9666
Characteristic | Specifications |
---|---|
SPECIAL FEATURES | DESIGNED FOR COLD WATER,ITEM IS EQUIPPED W/SPIRAL TURBULATORS WITHIN TUBES;DESIGNED TO PROVIDE SHOCKPROOF SHIPBOARD SERVICE;TUBE DATA,COPPER,48,8 ROWS,STAGGERED,5/8 IN.OD;FIN DATA,COPPER,84 PER FT,MECHANICALLY BONDED TO TUBES;SUPPLY AND RETURN CONNECTIONS ARE AT THE SAME END;CONNECTION DATA,SUPPLY CONNECTION DATA,PIPE,1,FLANGED,3/4 IN.IPS,RETURN CONNECTION DATA,PIPE,1,FLANGED,3/4 IN.IPS;EQUIPPED W/CASING,DRILLED,3/8 IN.DIA HOLES;1.35 SQ FT NET FACE AREA;SURFACE AREA IN SQ FT NOT RATED;OVER-ALL DIM.,36 IN.LG,21 IN.W,15-1/8 IN.THK;300 LB RATED HYDROSTATIC TEST PRESSURE;DATA REGARDING A TYPICAL MFR,MCINTYRE ENGINEERING CO,SAN FRANCISCO,CALIF,CODE NO. 87103,SIZE 43-DW-A; |
NONDEFINITIVE SPEC/STD DATA | A TYPE |