NSN 6110-00-542-2202

Part Details | ELECTRICAL MOTOR THERMAL-OVERLOAD PROTECTOR


6110-00-542-2202 A protective device specifically designed to prevent damage to an electrical motor due to failure of the motor to start, severe overloading of short duration, too frequent starting, high ambient temperature, high or low circuit voltages, failure of ventilation or any combination thereof. It is designed to be either automatically or manually reset. Excludes CIRCUIT BREAKEY; SWITCH (1), THERMOSTATIC; HEATER, THERMAL RELEASE; and RELAY (1), THERMAL.

Alternate Parts: 1034300, 1034300, SKA33, SKA-33, 6110-00-542-2202, 00-542-2202, 6110005422202, 005422202

Supply Group (FSG) NSN Assigned NIIN Item Name Code (INC)
61JAN 01, 196300-542-220260869 ( PROTECTOR, THERMAL-OVERLOAD, ELECTRICAL MOTOR )
REFERENCE DRAWINGS & PICTURES

Cross Reference | NSN 6110-00-542-2202
Part Number Cage Code Manufacturer
103430077068ALLIED-SIGNAL INCDBA ALLIED-SIGNAL AEROSPACE CO
103430059364HONEYWELL INTERNATIONAL INC.DBA HONEYWELL
SKA-3382647SENSATA TECHNOLOGIES, INCDIV SENSATA ATTLEBORO

Technical Data | NSN 6110-00-542-2202
Characteristic Specifications
OVERALL HEIGHT0.520 INCHES NOMINAL
OVERALL DIAMETER0.684 INCHES NOMINAL
SPECIAL FEATURESOPERATING TEMP OF TRIP AT 148 DEG C AND RESET AT 115 DEG C; ULTIMATE TRIP CURRENT 0.86 AMPS AT EFFECTIVE PROTECTOR AMBIENT OF 100 DEG C; FIRST CYCLE TRIP CURRENT 2.35 AMPS REQUIRED TO OPEN THE PROTECTOR IN 9-22 SECONDS AT EFFECTIVE PROTECTOR AMBIENT OF 25 DEG C